Alarm Input/Control Output Points
Configuring Alarm Inputs via Trigger Action Rules 19-5
Configuring Alarm Inputs via
Trigger Action Rules
You can configure the LX-Series unit using the console CLI or by
using the Graphical User Interface (GUI). You can configure the
Alarm Inputs function using Signal-Notice or by using the CLI
commands Trigger-Action-Rule. The following examples set up
an Alarm Input using CTS and utilize the port DTR Control
Output as the controlling voltage on Port 10. Additionally, when
the Trigger events occur, an SNMP message is generated.
X To configure alarm inputs via trigger action rules
1. Create a trigger:
Example InReach:0 >> config
Config:0 >> trigger
Trigger-Action:0 >> trigger name pa10ctsh
Trigger-pa10ctsh:0 >> signal port 10 cts high
Trigger-pa10ctsh:0 >> exit
Trigger-Action:0 >> trigger name pa10ctsl
Trigger-pa10ctsl:0 >> signal port 10 cts low
Trigger-pa10ctsl:0 >> end
InReach:0 >>
2. Create an action:
Example InReach:0 >> config
Config:0 >> trigger
Trigger-Action:0 >> action name pa10ctsh
Action_pa10ctsh:0 >> command notify facility user
priority notice message CTS is H on port name Lab1
Action_pa10ctsh:0 >> exit
Trigger-Action:0 >> action name pa10ctsl
Action_pa10ctsh:0 >> command notify facility user
priority notice message CTS is L on port name Lab1
Action_pa10ctsl:0 >> end
InReach:0 >>
See the
Signal-
Notice
Example
for more
informa-
tion.
Names of
the form
pa#ctsu
p,
pa#ctsd
n are
reserved
for Signal
Notice
setup.