Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Enabling and Disabling Audible Alarms 15-5
X To configure a descriptive name for any Alarm Input
in the LX-7204T/7304T
Use the following
Privileged command syntax:
Syntax hdam alarm <alarm_name_1> name <alarm_name_2>
hdam alarm port <port_number> slot <slot_number>
point <point_number> name <new_name>
where
Examples
Enabling and Disabling Audible Alarms
Use the following commands to enable and disable the audible
alarm for a specific alarm or for multiple alarms.
X To enable and disable audible alarms
1. Use the following command syntax to enable and disable
the audible alarm for either a specific alarm:
Syntax hdam alarm port <port_number> slot [<slot_list>|all]
point [<
point_list>|all] audible enable
hdam alarm port <
port_number> slot [<slot_list>|all]
point [<
point_list>|all] no audible
alarm_name_1 Name of the alarm input to rename
alarm_name_2 New alarm name to assign to the alarm input
L The name must start with a letter, and the
remainder of the name can contain only letters
and/or numbers and/or underscores.
port_number Specifies the individual LX port to which the
LX-7204T/7304T is attached
slot_number Number of the slot for which to configure a name
point_number Specifies a specific point for which to configure a name
new_name New name for the point
Config:0 >>hdam alarm 5_4_20 name BankVaultDoor
Config:0 >>hdam alarm port 5 slot 4 point 20 name BankVaultDoor
InReach:0 >>hdam alarm port 5 slot 4 point 20 name BankVaultDoor